Description
Sikaflex-400 Fire from Sika Australia is a one-part, moisture-curing polyurethane sealant. Sika designs it for fire rated movement and connection joints. The published CSIRO test (FSP 1819) covers 20mm control joints in 150mm concrete walls, tested to AS 1530.4. It stays elastic enough to take ±35% joint movement.
Fire ratings for sealed joints depend on joint width, depth, backing material and the wall around it, so treat it as part of a tested fire stopping system, not as a stand-alone product.
Technical Specifications
| Manufacturer | Sika Australia |
|---|---|
| Composition | 1-part polyurethane, moisture curing |
| Colour | Grey |
| Packaging | 600ml foil pack (sausage), 20 per box |
| Density | About 1.40 kg/l (ISO 1183-1) |
| Movement capability | ±35% (ASTM C719); ±25% (ISO 9047) |
| Secant tensile modulus | About 0.30 N/mm² at 100% elongation (23°C); about 0.45 N/mm² (-20°C) |
| Elastic recovery | About 85% (ISO 7389) |
| Tear propagation resistance | About 5.0 N/mm (ISO 34) |
| Sag flow | About 0mm (20mm profile, 50°C) |
| Skinning / tooling time | About 180 / 150 minutes (23°C, 50% RH) |
| Curing rate | About 2.5mm per 24 hours (23°C, 50% RH) |
| Application temperature | Air and substrate +5°C to +40°C; substrate at least 3°C above dew point |
| Service temperature | -40°C to +70°C |
| Test reports listed by Sika | AS 1530.4 (CSIRO FSP 1819, CSIRO FSP 1839, Exova 376610B); ASTM C920-14 Class 35; EN 13501-2; EN 15651-1; ISO 11600 |
| Shelf life | 12 months from production, unopened, dry, +5°C to +35°C |
Fire Test Result (CSIRO FSP 1819)
Tested to AS 1530.4-2014 in a 150mm thick concrete wall. Each joint was 20mm wide, sealed 10mm deep over a 30 x 20mm polyurethane foam backing rod and finished flush. The FRLs below apply only when installed as tested.
| Sealant applied | FRL achieved |
|---|---|
| Both faces of the wall | -/240/180 |
| Non-fire side only | -/240/120 |
| Fire side only | -/240/0 |
Coverage
| Joint width x depth | Metres per 600ml sausage |
|---|---|
| 10 x 10mm | 6 |
| 15 x 10mm | 4 |
| 20 x 10mm | 3 |
| 25 x 12mm | 2 |
| 30 x 15mm | 1.3 |
How to Apply
- Prepare the joint: surfaces must be sound, clean and dry, free of dust, oil, laitance, old sealant and loose paint. Saw-cut new joints and flush away slurry.
- Prime if required: for critical joints, prime porous surfaces with Sika Primer-3 N or Primer-210 and wait at least 30 minutes.
- Insert the backing rod to the depth that matches the tested fire configuration for your joint.
- Gun the sealant into the joint so it fully contacts both sides with no trapped air.
- Tool it firmly against the joint sides straight away, using Sika Tooling Agent N or water. Do not use solvent-based tooling products.
Important Notes
- Fire ratings are only valid for the tested joint width, depth, backing and wall type. Confirm the system with your certifier against the National Construction Code requirements for the job.
- Not for natural stone, bitumen, natural or EPDM rubber, swimming pools, joints under water pressure or permanent immersion.
- Keep uncured sealant away from alcohol-based products, which can upset curing.
- Sika’s Safety Data Sheet classifies it as a Warning (H373, organ damage through prolonged or repeated exposure if swallowed). Read the SDS under the Documents tab before use.
- Clean tools with Sika Remover-208 straight after use. Cured sealant can only be removed mechanically.