Description
Firecryl FR is Soudal‘s intumescent fire sealant for the gaps that matter in fire-rated walls. It is a plasto-elastic sealant made from acrylic dispersion that swells when heated above 120°C, helping to stop fire and smoke getting through a joint. Because it is water based, it is easy to tool, cleans up with water while fresh, and can be painted once cured.
For Australian work, Soudal publishes Jensen Hughes fire assessment report 260315, which assesses Firecryl FR linear gap seals to AS 1530.4:2014 and AS 4072.1:2005. It covers plasterboard stud walls and aerated concrete walls and floors. The ratings depend on wall type, gap width and sealant depth, and apply only when installed as tested. The report is an assessment based on European EN 1366-4 fire tests, not a new AS 1530.4 test, and it says building certifiers must determine whether the system suits the job. Talk to a fire engineer or certifier before installing any fire-rated product.
Technical Specifications
| Base | Acrylic dispersion, intumescent |
|---|---|
| Curing | Physical drying |
| Skin time (23°C / 50% RH) | About 20 minutes |
| Density | About 1.57 g/ml |
| Movement capability (ISO 11600) | About 12.5% |
| Shrinkage (DIN 52451) | About 15% |
| Application temperature | 5°C to 30°C |
| Temperature resistance (cured) | -20°C to 80°C |
| Intumescence | Expands when exposed to temperatures above 120°C |
| Colour and pack | Grey, 310ml cartridge |
| Shelf life | At least 12 months unopened, dry, 5°C to 25°C; protect from frost |
| Hazard class | Non-hazardous, not dangerous goods (SDS) |
Fire Ratings in Report 260315
The wall or floor itself must be tested or designed for the required FRL. Ratings apply only when installed as tested; see the full report under the Documents tab for every option.
| 75mm metal stud wall, 1 × 13mm fire-rated plasterboard each side, 50mm rockwool in the cavity | 20mm max gap to the adjacent solid wall or floor, Firecryl FR 12.5mm deep both sides, no backing: -/60/60 (vertical joint with 0mm gap: -/60/30) |
|---|---|
| 100mm metal stud wall, 2 × 13mm fire-rated plasterboard each side, 50mm rockwool in the cavity | 20mm max gap to the adjacent solid wall or floor, Firecryl FR 25mm deep both sides, no backing: -/120/120 (vertical joint with 0mm gap: -/120/90) |
| 200mm aerated concrete wall (550 kg/m³) | 30mm max gap, Firecryl FR 20mm deep on the fire-exposed face over 180mm Soudafoam FR HY backfill: -/240/240 (fire from the sealant side only) |
| 150mm aerated concrete floor (550 kg/m³) | 30mm max gap, Firecryl FR 20mm deep on the top or bottom side over 130mm Soudafoam FR HY backfill: -/240/240 |
Where to Use
- Linear gaps in fire-rated plasterboard and aerated concrete walls
- Fire-resistant, smoke-tight joints indoors
- Filling cracks in concrete and plasterwork (no fire rating claimed)
- Joints that will be painted with water-based paint
How to Apply
- Prepare: surfaces must be clean, dry and free of dust. Prime very porous surfaces with Firecryl FR diluted 1 part to 2 parts water.
- Set the depth: install any backing and sealant depth exactly to the tested design you are relying on.
- Apply: use a manual or pneumatic caulking gun, between 5°C and 30°C.
- Finish: tool with a spatula or putty knife, using soapy water before it skins.
- Clean up: remove fresh sealant from tools and surfaces with water.
Important Notes
- Not suitable for natural stone, bitumen, glass or metal; test adhesion on each surface.
- Shrinks about 15% as it dries (DIN 52451).
- Do not use where it will be continuously under water.
- Confirm the required FRL and joint design with your fire engineer or certifier under the National Construction Code.